NICET Level 1 ITM of Water-Based Systems (A+ Guaranteed) 2024 UpdateNICET Level 1 ITM of Water-Based Systems (A+ Guaranteed) 2024 Update
Who is
... [Show More] responsible for the inspection, testing, maintenance and impairment of a water based fire protection system? correct answers The Property owner or designated representative
Who's responsibility is it to provide accessibility to components of a water based fire protection system? correct answers The property owner or designated representative
Who shall correct or repair deficiencies or impairments found during the inspection, test and maintenance required by standard? correct answers The property owner or designated representative
Who is qualified to preform the corrections and repairs of a water based fire protection system? correct answers Qualified maintenance personal or a qualified contractor
A permanently marked metal or rigid plastic information sign shall be placed at the system control riser supplying an antifreeze loop, dry system, preaction, or auxiliary system control valve? correct answers An Information Sign,
Records made during all inspections, tests and maintenance shall be made available to who upon request? correct answers The Authority Having Jurisdiction
All records shall be maintained by? correct answers The Property Owner
How long should subsequent records be retained? correct answers 1 year,
After the testing and reinstallation of plugs and caps for auxiliary drain and test valves, what action is required? correct answers Shall be restored to full operational condition,
To avoid false alarms where a supervisory service is provided the alarm receiving facility shall be notified by the property owner or designated representative before? correct answers conducting any test or procedure that could result in the activation of an alarm,
Sprinklers shall be inspected when and how? correct answers Shall be inspected from the floor level annually
Sprinklers shall not show signs of the following? correct answers leakage; shall be free of corrosion, foreign materials, paint, and physical damage; and shall be installed in the correct orientation
Sprinklers installed installed in concealed spaces such as above ceilings shall what? correct answers Shall not require inspection,
Sprinklers installed in areas that are inaccessible for safety considerations due to process operations shall be inspected? correct answers During each scheduled shutdown
The supply of spare sprinklers shall be inspected when? correct answers Annually,
A spare sprinkler wrench shall be required for what? correct answers Every type of sprinkler,
Sprinkler pipe and fittings shall be inspected from where and when? correct answers Annually from from the floor level,
Sprinkler Pipe hangers and seismic bracing shall be inspected? correct answers Annually from the floor level
Gauges on a wet pipe sprinkler system shall be inspected? correct answers Monthly,
Gauges on a dry, preaction system, and deluge systems shall be inspected? correct answers Monthly
When the gauge near the compressor is reading higher than the gauge near the dry pipe valve, the air line shall be what? correct answers Taken out of service
Waterflow alarm and supervisory alarm devices shall be inspected? correct answers Quarterly
The hydraulic design information sign for hydraulically designed systems shall be inspected? correct answers Quarterly
The information sign shall be inspected? correct answers Annually,
Where sprinklers have been on service for 50 years shall be? correct answers Replaced
Sprinklers manufactured prior to 1920 shall be? correct answers Replaced
Sprinklers manufactured using fast-response elements that have been in service for 20 years shall be? correct answers Replaced or tested at 10 year intervals
Representative samples of solder-type sprinklers with a temperature classification of extra high (325*F) or greater that are exposed to semi continuous to continuous maximum allowable ambient temperature conditions shall be? correct answers Tested at 5 year intervals
Dry sprinklers that have been in service for 10 years shall be? correct answers Tested
Where sprinklers are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, on a five years basis shall be? correct answers replaced or representative sprinkler samples shall be tested,
Gauges shall be replaced every? correct answers 5 years [Show Less]