If a Balancing Authority does not comply with the Control Performance Standard, the
Balancing Authority is not permitted to provide which of the
... [Show More] following for any other
Balancing Authority entities?
Regulation of other services related to control performance
1. It is the obligation of each Balancing Authority to fulfill its commitment to the
Interconnection and not ________ the other balancing Authorities in the
Interconnection
Burden
A Balancing Authority is performing Overlap Regulation Service for another
Balancing Authority. Which of the following statements applies to the Balancing
Authority providing this service?
The Balancing Authority's Frequency Bias Setting shall be modified to reflect the
combined Frequency Bias Setting of both Balancing Areas.
Balancing Authority A is currently reading a system frequency of 59.95 Hz. Its Net
Actual Interchange is +100 MW and its Net Scheduled Interchange is +200 MW. If
Balancing Authority A's frequency bias setting is 100 MW/0.1 Hz, Balancing Authority
A's AGC is pulsing its generators to do what?
Increase MW output
Which of the following is a Real-time measurement of a Balancing Authority's control
performance
BAAL
Each Balancing Authority shall monitor which of the following against two standards:
CPS1 and BAAL?
Control performance
In the calculating of CPS1, which of the below conditions would contribute to ta
favorable score?
Negative ACE when frequency is high,
positive ACE when frequency is low.
If the frequency bias setting is a higher value than the frequency response of a
Balancing Authority and a frequency decline is caused by a sudden loss of
generation is an external balancing area, what will be the result?
A- The ACE will be a negative value and AGC will increase generation
Which statement best describes the CPS1 requirement?
The Responsible Entity shall operate such that its CPS1 is greater than or equal to
100% for the preceding 12 month period.
To be in compliance with the BAL-001 requirements, a Balancing Authority must
have which of the following?
CPS1 greater than or equal to 100% and ACE does not exceed the BAAL more than
30 consecutive minutes
Actual System Frequency (FA) is 60.03 Hz, a Balancing Authority is undergenerating slightly to prepare for an upcoming interchange transaction. What is the
Balancing Authority doing?
The BA is helping the Interconnection Frequency.
You are a Balancing Authority Operator. A neighboring Balancing Authority in the
Interconnection suddenly had a 500 MW generator to trip off line by generator [Show Less]